Purpose. Calculation and experimental researches of electro-thermal resistibility of the pre-production thin-walled sheet models of outward roof of height technical buildings from stainless steel are easily soiled 12Х18Н10Т to direct action on them rationed by the International Standard IEC 62305-1-2010 aperiodic impulse of current of short bow of artificial lightning of temporal form 10/350 μs with the proper admittances on his peak-temporal parameters (PTP). Methodology. Electrophysics bases of technique of high voltage and large impulsive currents (LIC), and also scientific and technical bases of planning of high-voltage impulsive devices and measuring methods in them LIC with followings below extreme PTP: amplitude of impulse of current of ImL=200 кА (with admittance ±10 %); integral of action of impulse of current of JL=10·106 A2·s (with admittance ±35 %); %); duration of wavefront current of T1=10 μs (with admittance ±20 %); time, proper amplitude of impulse of current of ImL, tmL≤24 μs (with admittance ±20 %); duration of flowing of impulse of current of T2=350 μs (with admittance ±10 %). Results. The results of evaluation calculation and experimental researches of electro-thermal resistibility of the indicated pre-production sheet models are resulted measuring in the plan of 0,5 x 0,5 m from stainless steel are easily soiled the 12Х18Н10Т thickness of 1 mm to action on them of aperiodic impulse of current of short blow of artificial lightning with rationed PTP on the requirements of the International Standard IEC 62305-1-2010. In high current experiments amplitude of ImL of the aperiodic rationed impulse of current of artificial lightning of temporal form of T1/T2=15 μs/315 μs changed in the range of (100-184) кА. The integral of action of JL of impulse of current for I-IV of levels of protection of lightning of technical objects (TO) numeral made from 2,32·106 А2·s to 7,88·106 А2·s, and the flowing through the probed pre-production steel models electric charge of qL numeral changed from 44,2 Kl to 81,3 Kl. It is shown that direct influence rationed by the International Standard IEC 62305-1-2010 impulse of current of short blow of artificial lightning with in-use PTP on the indicated pre-production steel models causes in them the rounded small hole of melting of surface of coverage a depth no more than 50 μm and diameter no more than 60 mm. The results of calculation and experiment coincide within the limits of 5 %. Originality. First in world practice on the unique generator of LIC of short blow of artificial lightning of type of GITM-10/350 experimental researches of electro-thermal resistibility of pre-production sheet models of outward roof are conducted TO of stainless steel 12Х18Н10Т is easily soiled to direct action on them of impulses of current of an artificial storm air spark digit with extreme parameters. Practical value. Drawing on the got results in practice of protection height TO from linear lightning will allow substantially to promote their functional and fire-prevention safety in the conditions of direct action on them of the plasma ductings of high current storm air spark discharge.
artificial lightning impulse current of temporary shape 10/350 μs, thin-walled coverage made of stainless steel, electro-thermal effect of lightning current to the steel cover, radius and depth of penetration of the steel wall coverage, calculation and experimental estimation of damage zone of coverage, 621.3.022, calculation and experimental estimation of damage zone of coverage, электротермическое действие тока молнии на стальное покрытие, electro-thermal effect of lightning current to the steel cover, тонкостенное покрытие из нержавеющей стали, 537.311.8, 621.313, thin-walled coverage made of stainless steel, TK1-9971, импульс тока искусственной молнии временной формы 10/350 мкс, artificial lightning impulse current of temporary shape 10/350 μs, радиус и глубина зоны проплавления стенки стального покрытия, Electrical engineering. Electronics. Nuclear engineering, radius and depth of penetration of the steel wall coverage
artificial lightning impulse current of temporary shape 10/350 μs, thin-walled coverage made of stainless steel, electro-thermal effect of lightning current to the steel cover, radius and depth of penetration of the steel wall coverage, calculation and experimental estimation of damage zone of coverage, 621.3.022, calculation and experimental estimation of damage zone of coverage, электротермическое действие тока молнии на стальное покрытие, electro-thermal effect of lightning current to the steel cover, тонкостенное покрытие из нержавеющей стали, 537.311.8, 621.313, thin-walled coverage made of stainless steel, TK1-9971, импульс тока искусственной молнии временной формы 10/350 мкс, artificial lightning impulse current of temporary shape 10/350 μs, радиус и глубина зоны проплавления стенки стального покрытия, Electrical engineering. Electronics. Nuclear engineering, radius and depth of penetration of the steel wall coverage
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 2 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Average | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |