handle: 11583/2304169
The aim of this paper is to perform an analysis of the shunt Active Power Filter (APF) operating with unbalanced loads. The impact of the load imbalance on the APF performance is mathematically demonstrated and validated with experimental results using a 25 kVA shunt APF prototype. The APF operation in such conditions is affected by the appearance of DC-link voltage ripple at twice the grid frequency. As consequence, the source currents become distorted and the APF performance deteriorates. Based on this fact, a new control scheme is proposed to avoid high voltage ripple in the DC link, without increasing the DC-link capacitance.
active power filter, Unbalanced Load, Electrical engineering. Electronics. Nuclear engineering, Voltage Loop Control, TK1-9971
active power filter, Unbalanced Load, Electrical engineering. Electronics. Nuclear engineering, Voltage Loop Control, TK1-9971
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 8 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Average | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |