Very fast transient overvoltages (VFTO) are caused by disconnector switching operations within a gas insulated substation (GIS). The very fast transient overvoltages contains very high frequency components in the order of several 10psilas of MHz and may cause high frequency oscillations in the transformer windings, leading to possible overstressing of the transformer insulation. By modelling a gas insulated substation as very short transmission lines with an electromagnetic transient programme it is possible to predict the magnitude of these fast transients and their high frequency components. In this paper, PSCAD/EMTDC was used to model the switching operation of disconnectors in a GIS installation.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 10 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Top 10% | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |