This paper analyses the frequency support characteristics of multi-terminal VSC-HVDC (MTDC) schemes using the energy transferred from wind turbine rotating mass and other AC systems. An alternative coordinated control (ACC) scheme, which gives priority to a frequency versus active power droop fitted to onshore VSCs is proposed to: (i) transfer wind turbine recovery power to undisturbed AC grids and (ii) allow correct control operation of MTDC systems during multiple power imbalances on different AC grids. The fast frequency response capability of MTDC systems equipped with the proposed ACC scheme is compared against a coordinated control (CC) scheme, which uses a frequency versus DC voltage droop. The frequency control schemes are demonstrated on an experimental test rig which represents a 3-terminal HVDC system. Also, the MTDC frequency support capability when wind farms do not provide extra power is tested using a 4-terminal HVDC system.
TA
TA
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 99 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Top 1% | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Top 1% |