Contamination deposits on arrester housings when wetted can cause external flashovers and, by disturbing the voltage distribution on the internal gaps, can lower the power frequency sparkover of the arresters. It has been found that the conditions that produce the lowest external flashover often do not cause the greatest reduction in sparkover. Separate tests are needed to adequately test the flashover of external insulation and the internal sparkover of an arrester. A proposed test is being developed for checking the sparkover characteristic of a wet, contaminated arrester.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 1 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |