Electrical arc furnaces (EAF) are commonly employed in industry to produce molten steel by melting iron and scrap steel. EAF can be a source of power quality problems and a potential threat to nearby generators. In this paper, the power quality problems induced by a 40 MVA EAF located in the Tennessee power system solved by FACTS and energy storage system (ESS) technologies is studied. How EAF operation can affect a power system is analyzed by giving a detailed discussion about the function of X/R ratio. A cascade-multilevel converter (CMC) based STATCOM with high bandwidth is proposed for EAF induced voltage fluctuation mitigation. Simulation and experimental results show that the FACTS and ESS technology can efficiently and rapidly solve the EAF induced power quality problems
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 2 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Average | |