This paper presents a new, simple and efficient protection technique which is based on negative sequence currents. Using this protection technique, it is possible to detect minor internal turn-to-turn faults in power transformers. Also, it can differentiate between internal and external faults. The discrimination is achieved by comparing the phase shift between two phasors of total negative sequence current. The new protection technique has been studied via an extensive simulation study using PSCAD®/EMTDC™ software in a three-phase power system and also has been compared with a traditional differential algorithm. The results indicate that the new technique can provide a fast and sensitive approach for identifying minor internal turn-to-turn faults in power transformers.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 20 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Top 10% | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |