Stray losses in structural solid steel parts of three-phase power transformer are predicted using 3D finite element method (FEM). The computation is made under time harmonic steady state load condition, treating the transformer core magnetizing characteristic as non-linear. Various kinds of modeling of the thin steel plates for estimating stray losses due to leakage magnetic field are applied and their results are discussed. Numerically computed stray losses are compared with those measured in practice.
power transformer; eddy current losses; finite elemente, finite elemente, power transformer, eddy current losses
power transformer; eddy current losses; finite elemente, finite elemente, power transformer, eddy current losses
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 8 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |