The protection of busbar demands high integrity and high speed relaying scheme. This paper presents a new differential relaying scheme for the protection of busbar. The proposed scheme depends on the difference of the value of incoming and outgoing line currents of the respective phase at a particular bus. The proposed scheme has been tested extensively using the PSCAD/EMTDC software package with fault data generated, by modeling the existing 230 kV Indian power transmission systems. The proposed scheme provides stability against external faults, more sensitivity towards high resistance faults and better reliability in discriminating in-zone and out of zone faults. Moreover, the proposed scheme avoids the effect of early & severe CT saturation during heavy through faults.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 5 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |