This paper deals with the research of FACTS devices, specifically TCSC regulators. In the research, the NEPLAN program compiles a mathematical model of the TCSC system for the control of oscillations and the improvement of the dynamic stability of the transmission system. The TCSC element is implemented in the design in two places, namely in stations with generator outlets. The first outlet is the Mochovce nuclear power plant and the second on the outlet line of the Vojany thermal power plant. The height is mainly focused on reducing oscillations in short circuits. The result is the processing of dynamic stability data at a set short circuit with and without a TCSC device, as well as how this affects the CCT (Critical clearing time).
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 0 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Average | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |