doi: 10.1109/77.783387
We report on test results for a single phase, 60-Hz, 13.8 kV/6.9 kV, 1-MVA high temperature superconducting (HTS) transformer which was completed in February, 1998. This transformer models in many ways a full scale section of a 30-MVA HTS commercial transformer design. The transformer windings are cryocooled in the range of 25 K and are made with a low-cost, surface-coated BSCCO-2212 conductor. Heat leaks are reduced using a liquid nitrogen thermal ballast and reservoir. The use of high temperature superconductors can substantially reduce transformer losses, weight, size, noise and potential fire and environmental hazards. Designs promise stable operation through faults without thermal degradation, and at temperatures that allow efficient and reliable refrigeration.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 56 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Top 10% | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 1% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Top 10% |