doi: 10.1109/60.4749
Details on four types of shaft voltages are given, with emphasis on the occurrence, transmission and damaging mechanisms of shaft voltages from static excitation systems. A model for numerical simulation is presented and simulation results are compared with tests performed on a statically excited 1200 MVA turboset. A program of countermeasures is proposed, mainly including a type of passive RC-circuit connected through a grounding brush on the exciter end of the generator. This set of counter measures has successfully been tested on two turbosets, one of 190 MVA and one of 1200 MVA, showing the following advantages: reduction of shaft voltages to a harmless level; good access (even in nuclear power plants), low maintenance costs and long brush life; operation with or without grounding brush on the turbine end of the generator is possible; and easy monitoring is an additional feature. >
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 68 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Top 1% | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 0.1% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |