doi: 10.1109/59.736278
A new dynamic reactive load model for power system dynamic voltage stability studies is introduced in this paper. The model is measurement-based and incorporates the effect of voltage regulating equipment, specifically, switched distribution capacitor banks and subtransmission substation on-load tap changer transformers. A set of parameters that reflect these delayed-action devices are involved in the proposed model. A parameter estimation scheme is introduced with the aim of minimizing errors between model and collected data at two Pennsylvania Power and Light Company 230/64 kV substations. System simulation is also carried out based on the estimated parameters.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 21 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Top 10% | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |