handle: 11577/2524142 , 11577/2529219
Abstract This paper presents recent measurements of heat transfer coefficient obtained during condensation of R32 inside a commercial brazed plate heat exchanger (BPHE). The experimental data show the effect of refrigerant mass velocity, vapor quality, temperature difference (saturation-to-wall) and inlet vapor superheating. In particular, the specific mass velocity is varied between 15 and 40 kg m −2 s −1 and the outlet vapor quality between 0.0 and 0.65, while inlet vapor superheating goes from 5 to 25 K. The saturation temperature is kept constant at around 36.5 °C, which can be considered a usual temperature level for water cooled heat pump applications. The present authors provide a numerical procedure to calculate the condensation heat transfer in the BPHE, accounting also for the superheating effect. This model is assessed by comparisons with the experimental measurements relative to R32, R410A, and R744.
condensation, BPHE, R32; Condensation; Plate Heat exchanger, R32, 530
condensation, BPHE, R32; Condensation; Plate Heat exchanger, R32, 530
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 29 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Top 10% | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Top 10% |