This paper presents the methodologies for incipient fault detection in power transformers both off-line and on-line. An artificial neural network is used to detect faults off-line with dissolved gas analysis reports of transformers and whereas wavelet transforms are being used for on-line fault detection. The accuracy in fault detection through artificial neural networks is compared with Rogers ratio method using the analysis of experimental oil samples for power transformers of power companies in Andhra Pradesh, India. The Wavelet transform techniques have been developed with different mother wavelets to detect incipient faults and to distinguish between incipient fault and short circuit fault. Further their performances with different mother wavelets are compared.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 35 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Top 10% | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Top 10% |