doi: 10.1002/prs.10479
AbstractA natural gas fired industrial oven exploded during an attempted restart. The explosion was caused by the accumulation of natural gas during the hours preceding the restart. The oven had a fully‐automated control system, and the start, shutdown, and restart were controlled by process controls and a flame safeguard system. A malfunction of the flame detector allowed the automated controls to complete the start sequence and establish normal operating status without a flame present in the burner. The ultraviolet flame sensor gave a false positive signal, which allowed unburned natural gas to enter the oven. This investigation explored the cause of the incident and the failure modes of the flame detector. Recommendations are included for preventing this type of accident. © 2011 American Institute of Chemical Engineers Process Saf Prog, 2011
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 2 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |