This paper deals with a new detection method based on three-phase vector operation for voltage sag. The detection method is applicable to a protection system using a high-speed interruption system which protects distributed generators and critical loads in a customer's facility. The algorithm and merits of this method are explained in detail. The detection characteristics are then analyzed using the ATP (Alternative Transients Program) and are confirmed using a real-time digital simulator, and it is shown that the method is useful for detecting voltage sag. © 2005 Wiley Periodicals, Inc. Electr Eng Jpn, 152(4): 34–41, 2005; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20117
critical load, system interconnection, 自家用発電設備, high speed circuit breaker, three-phase to two-phase transformation, non-utility generation facility, voltage sag, 瞬時電圧低下, 重要負荷, 高速遮断器, 三相二相変換, 系統連系
critical load, system interconnection, 自家用発電設備, high speed circuit breaker, three-phase to two-phase transformation, non-utility generation facility, voltage sag, 瞬時電圧低下, 重要負荷, 高速遮断器, 三相二相変換, 系統連系
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 0 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Average | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |