doi: 10.7250/pee.2016.011
In the paper, the power lines with flat arrangement of phases are considered. At the end of untransposed power lines, the unbalanced voltage appears. As an alternative to transposition, unbalanced load can be applied. Considerable difference of phase loads is the shortcoming of this method. A special increase of mutual inductance among outer phases would be a proper alternative if the way of its implementation would be found. Zero sequence is smaller for the line with overhead ground wires (OGW), especially when OGW is above the middle phase. Parallel lines have considerable mutual Fortesque impedances of all sequences, the most of them being zero sequence. The impact of parallel lines can be weakened by additive measures. Fault analysis of untransposed lines can be reduced to that of transposed.
Parallel power lines; relay protection; transmission line; transposition; unbalanced voltage.
Parallel power lines; relay protection; transmission line; transposition; unbalanced voltage.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 0 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Average | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |