doi: 10.3233/saem250040
According to statistics, short circuit faults in transformer windings account for 70% to 80% of the total faults. Therefore, the study of the short circuit withstand capability of transformers holds significant importance. This paper focuses on investigating the winding deformation and short circuit strength of a ODFPS-700000/750 single-phase four-column transformer during high-medium voltage operation and low-voltage side short circuit conditions. The influence of pads and struts offset on various aspects of windings is considered during the implementation. The paper presents the distributions of magnetic leakage field, current, winding deformation displacement, and electromagnetic forces under transformer short circuit conditions. This provides a novel approach for the verification of short circuit strength in large-scale transformer windings.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 0 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Average | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |