As one of the core equipment of high-voltage direct-current (HVDC) transmission system, the health status of passive MRTB would directly threaten the secure and stable operation of power system. Aiming at correctly getting the real-time operating status of passive MRTB , a new condition assessment method base on fuzzy theory is proposed and the corresponding device has been developed in this paper. After sampling the oscillating current, this method calculates arcing time by wavelet theory ,then fuzzy theory is used to judge the operating status of passive MRTB.