Correct operation of the protection system is of vital importance for the reliability and security of supply. Information of protection system faults is therefore important for different purposes such as quality of supply regulation and as input data to security and reliability analysis. This paper provides a comparative review of the Norwegian and Finnish fault statistics for line and transformer protection systems at the voltage levels 132 - 400 kV for the period 1999 - 2004. Unwanted operation is the major fault type, particularly for transformer protection. Human causes dominate by roughly 50 %, technical faults count for 20 - 30 % while there are large portions of faults where the cause is not identified. In Norway 20 % of the total energy not supplied at these voltage levels are caused by the protection. The corresponding portion in Finland is only 4 %.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 21 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |