A new fault location algorithm for distribution network is proposed based on the wide-area synchronizing information. The algorithm is based on the distributed parameters model in the small current neutral grounding system, and constructed a fault location function according to the relationships between the fault current and fault distance, which fully utilizes synchronized samples of currents and voltages from the two ends of a line. If assumed fault distance, a corresponding fault current can be obtained. And the maximum fault current can be obtained using the iterative search algorithm along the whole line, the distance corresponding to the maximum fault current is the actual fault distance. Simulation results show that the algorithm is reliable and accurate and can be extended for other types of faults.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 3 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Average | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |