Abstract This paper presents the experimental results of shell side dry expansion evaporation characteristics of ammonia on a triangular pitch plain tube bundle in a multi pass cross flow configuration evaporator. Heat exchanger had 4 passes with 3 plain tubes in each pass. The average bundle heat transfer coefficient showed better performance at −1.7 °C versus −20 °C. Heat transfer performance of individual passes were studied at saturation temperature of −1.7 and −20 °C, heat flux range of 5 to 45 kW m −2 and exit superheat temperature of 2 to 10 °C. Present data suggest that variation in bundle performance is less significant at lower heat fluxes with low degree of exit superheat. Top pass with maximum quality along the bundle height showed the least performance with increase in the degree of exit superheat.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 4 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Average | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |