Several methods have been proposed and investigated so far on mitigation of very fast transient overvoltages (VFTO) in gas-insulated switchgear (GIS). The state-of-the-art methods are primarily based on dissipation of the energy associated with electromagnetic waves that the VFTO originate from and are composed of. Present paper reports on an alternative concept of VFTO mitigation based on the principle of controlling voltage conditions preceding voltage breakdown in SF6 gas that leads to VFTO generation. The paper introduces different control algorithms and shows how the algorithms can limit VFTO maximum value and total number of voltage breakdowns during operation of the GIS disconnector. The concept is applied for mitigation of VFTO in ultra-high voltage GIS. As the study case, an 1100 kV test set-up is used as recently reported for Wuhan (China) GIS station, with the disconnector characteristics obtained from 1100 kV development tests.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 20 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Top 10% | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Top 10% | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Top 10% |