doi: 10.1049/cp.2015.0072
This paper describes an advanced LCC-HVDC model developed in PowerFactory for National Grid under the background of Western HVDC link in UK. Unlike most of the HVDC models in different simulation packages, this model explicitly incorporates the Automatic Filter Switching control and On-Load Tap Changer (OLTC) control. The automatic filter switching control is designed to limit the reactive power exchange between the converter station and the connected AC system at all power transfer levels to be within acceptable range. The OLTC is designed to dynamically control the firing angle at rectifier side and extinction angle at inverter side within their desirable ranges. Under the PowerFactory environment the DIgSILENT Programming Language (DPL) is written to carry out the system setup and the DIgSILENT Simulation Language (DSL) model is used to implement the controller designs.
| selected citations These citations are derived from selected sources. This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | 0 | |
| popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network. | Average | |
| influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically). | Average | |
| impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network. | Average |