STUDI ANALISIS KOORDINASI OVER CURRENT RELAY (OCR) DAN GROUND FAULT RELAY (GFR) PADA RECLOSER DI SALURAN PENYULANG PENEBEL

I Dewa Gde Agung Budhi Udiana; I G Dyana Arjana; Tjok Gede Indra Partha;
Open Access
  • Published: 01 Aug 2017 Journal: Majalah Ilmiah Teknologi Elektro, volume 16, page 37 (issn: 1693-2951, eissn: 2503-2372, Copyright policy)
  • Publisher: Universitas Udayana
Abstract
<jats:p>Short circuit causing over current problem and can might causing interference of the equipment performance such as distribution transformers also causing widespread disruption occurred. In resolving such interference is required as protection system on the distribution system. Seeing all above is needed coordination between the supporting component of the protection system which is consisted of Over Current Relay (OCR) and Ground Fault Relay (GFR). The research was conducted at PT. PLN (Persero) South Bali Area Network, INDONESIA on recloser in the feeder line of Penebel. OCR setting between the Relay feeder of Penebel, Recloser Celagi, Recloser Bakisan,...
Subjects
free text keywords: Recloser, Electrical engineering, business.industry, business, Fault (power engineering), Engineering, Relay, law.invention, law, Overcurrent, Over Current Relay (OCR), Ground Fault Relay (GFR), Protection, Short Circuit, Electrical engineering. Electronics. Nuclear engineering, TK1-9971